PNOZ s1 Safety relays Operating Manual-21393-EN-07
Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.
PNOZ s1 Safety relay PNOZ s1 The safety relay provides a safety-related interruption of a safety circuit. The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with } E-STOP pushbuttons } Safety gates For your safety } Only install and commission the unit if you have read and understood these operating instructions and are familiar with the applicable regulations for health and safety at work and accident prevention.
PNOZ s1 Safety features The relay meets the following safety requirements: } The circuit is redundant with built-in self-monitoring. } The safety function remains effective in the case of a component failure. } The correct opening and closing of the safety function relays is tested automatically in each on-off cycle. } The unit has an electronic fuse.
PNOZ s1 Installation Install base unit without contact expansion module: } Ensure that the plug terminator is inserted at the side of the unit. Connect base unit and PNOZsigma contact expansion module: } Remove the plug terminator at the side of the base unit and at the contact expansion module. } Connect the base unit and the contact expansion module to the supplied connector before mounting the units to the DIN rail.
PNOZ s1 Preparing for operation } Supply voltage Supply voltage AC DC } Input circuit Input circuit Single-channel Emergency stop without detection of shorts across contacts Safety gate without detection of shorts across contacts } Dual-channel Start circuit/feedback loop Start circuit/feedback loop Start circuit Feedback circuit Automatic start Manual start Operating Manual PNOZ s1 21393-EN
PNOZ s1 } Semiconductor output *Connect together the 0V connections on all the external power supplies Key } S1: E-STOP pushbutton } S2: Start button } : Switch operated } : Gate open } : Gate closed Information If a base unit and a contact expansion module from the PNOZsigma range are connected via the connector, no additional wiring is necessary. Operation The unit is ready for operation when the Power LED is permanently lit.
PNOZ s1 Status indicators Power, In1, In2 Input circuit is closed. Out Safety contacts are closed and semiconductor output Y32 carries a high signal. Reset 24 V DC is present at S34. Error indicators Fault Diagnostics: Plug terminator not connected } Remedy: Insert plug terminator, switch supply voltage off and then on again. Fault Diagnostics: Internal error, unit defective } Remedy: Switch supply voltage off and then on again, change unit if necessary.
PNOZ s1 Electrical data Max. overall cable resistance Rlmax Single-channel at UB DC Voltage at Input circuit DC Reset circuit DC Feedback loop DC Current at Input circuit DC Reset circuit DC Feedback loop Number of output contacts Instantaneous safety contacts (N/O) Inputs Number Semiconductor outputs Number Voltage Current Relay outputs Max. short circuit current IK Utilisation category In accordance with the standard Safety contacts, AC1 at Max. current Min. current Max.
PNOZ s1 Conventional thermal current while loading several contacts Ith per contact at UB DC Conv. therm. current with 1 contact Conv. therm. current with 2 contacts Times Switch-on delay With automatic reset typ. With automatic reset max. With automatic reset after power on typ. With automatic reset after power on max. With manual reset typ. With manual reset max. Delay-on de-energisation With E-STOP typ. With E-STOP max. With power failure typ. With power failure max. Recovery time at max.
PNOZ s1 Environmental data Protection type Mounting (e.g.
PNOZ s1 Safety characteristic data Operating mode EN ISO 13849-1: 2006 EN ISO 13849-1: 2006 PL Category Safety con- PL c tacts, instantaneous Cat. 3 EN IEC 62061 SIL CL SIL CL 2 EN IEC 62061 IEC 61511 IEC 61511 SIL PFD PFHD [1/h] 2,00E-07 SIL 2 5,95E-03 EN ISO 13849-1: 2006 TM [year] 20 All the units used within a safety function must be considered when calculating the safety characteristic data.
In many countries we are represented by our subsidiaries and sales partners. ... Please refer to our homepage for further details or contact our headquarters. Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de Internet: www.pilz.com Technical support +49 711 3409-444 support@pilz.