Datasheet

Electronic monitoring relays PMDsrange
Phase sequence monitoring
S1PN
NSG-D-2-029-2009-09Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
-2
Connection example
Key
` 1 = Cable cross section max. 4
mm
2
, on larger motor cables the
supply line should be fused!
M1
F2
U
B
K2
M 3 AC
U
V
W
1
H1
1L2
0V
L1
L2
L3
1L1
K2
S2
K2
S1
L1 L2 L3
22 24
11 12
21
14
S1PN
PE
Technical details S1PN
Electrical data
Supply voltage AC: 200 ... 240, 400 ... 500, 550 ... 690 V
Tolerance 85 ... 110 %
Frequency range AC 50 ... 60 Hz
Power consumption 200 ... 240 V: 8 VA; 400 ... 500 V: 15 VA;
550 ... 690 V: 20 VA
Utilisation category in accordance with
EN 60947-4-1
EN 60947-5-1
AC1: 240 V/0.1 ... 5 A/1200 VA
DC1: 24 V/0.1 ... 5 A/120 W
AC15: 230 V/2 A; DC13: 24 V/1.5 A
Output contacts 2 auxiliary contacts (2 C/O)
Contact material AgCdO, 3 µm gold plating for
low load range 1-50 V/1-100 mA
Contact fuse protection to EN 60947-5-1 Max. 6 A quick or max. 4 A slow