Datasheet

Electronic monitoring relays PMDsrange
True power monitoring
S1WP
1001903-EN-03-2015-07Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
-6
Technical details S1WP
Electrical data
Supply voltage DC: 24 V
AC/DC: 230 V
Tolerance DC: 85 ... 125 %
AC/DC: 25 ... 115 %
Frequency range 30 ... 400 Hz
Power consumption DC: 2 W at U
B
: 24 V
AC: 5 VA at U
B
: 230 V
Utilisation category in accordance with
EN 60947-4-1
EN 60947-5-1
AC1: 240 V/0.1 ... 5 A/1200 VA
DC1: 24 V/0.1 ... 5 A/120 W
AC15: 230 V/0.1 ... 1.8 A
DC13: 24 V/0.1 ... 1.5 A
Output contacts 1 auxiliary contact (C/O)
Contact material AgCdO, 3 µm gold plating for
low load range 1-50 V/1-100 mA
Contact fuse protection in accordance with
EN 60947-5-1
Max. 6 A quick or max. 4 A slow
Analogue measuring output Voltage: 0 ... ±10 V
Current: +4 ... + 20 mA
Analogue reaction time 60 ms
Linearity/switching accuracy < ±2 %
Measuring circuit
Measuring voltage 3 AC/DC: 0 ... 120, 0 ... 240, 0 ... 415, 0 ... 550 V
1 AC/DC: 0 ... 70, 0 ... 140, 0 ... 240, 0 ... 320 V
Frequency range 0 ... 1000 Hz
Adjustable limit values for measuring ranges See table
Max. measuring current 22 A at 100 % duty cycle
Max. overload 45 A/max. 3 s
Response time 0,1 ... 20 s selectable
Start-up suppression time 0,1 ... 30 s selectable
Current transformer requirements I = 1 A: 1,5 ... 7.5 VA, Class 3
I = 5 A: 2,5 ... 15 VA, Class 3
Environmental data
EMC EN 61000-6-2, EN 61000-6-4
Vibration in accordance with EN 60068-2-6 Frequency: 10 ... 55 Hz
Amplitude: 0.35 mm
Climatic suitability EN 60068-2-78
Airgap creepage in accordance with
Pollution degree
Overvoltage category
EN 60947-1
2
III
Rated insulation voltage 300 V
Rated impulse withstand voltage
Measuring circuit to remaining circuits
Auxiliary contact to remaining circuits
6.00 kV
4.00 kV
Ambient temperature 0 ... +55 °C
Storage temperature -40 ... +85 °C
Mechanical data
Cross section of external conductors
1 core flexible
2 core with the same cross section, flexible
with crimp connectors, no plastic sleeve
without crimp connectors or with TWIN crimp connectors
0.20 – 4.00 mm², 24 – 10 AWG
0.20 – 2.50 mm², 24 – 14 AWG
0.20 – 2.50 mm², 24 – 14 AWG
Torque setting for connection terminals 0.60 Nm (screws)
Mounting position Any
Housing material
Housing
Front
PPO UL 94 V0
ABS UL 94 V0