Datasheet
Electronic monitoring relays PMDsrange
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Single-phase current monitoring
S1IM
NSG-D-2-008-2009-09
Altdaten CMT
The S1IM current monitoring relay is
used to monitor the maximum current
values on heaters, lamps etc.
Approvals
Zulassungen
Unit features
Altdaten CMT
` 12 measuring ranges can be select-
ed from 0.002 to 15 A
` Reaction time can be set to up to 10
seconds
` Operates to either normally ener-
gised or normally de-energised
mode
` Galvanic isolation between measur-
ing and supply voltage
` UP version: measuring inputs are
not polarity-sensitive
Description
The current monitoring relay is en-
closed in an S-95, slimline housing.
There are 8 versions available for AC
operation and one for DC operation.
Features
` Relay outputs: 1 auxiliary contact
(C/O)
` 3 measuring circuits for 0.1 A, 2 A
and E, each with 4 different ranges
` Response value can be set from
20 % to 100 % of the measuring
range limit value
` Hysteresis factor can be set from
0.6 to 0.9 x I
on
` Fault latching or automatic reset
` LEDs for relay's switch status and
for supply voltage
The S1IM monitors for current values
exceeding a selectable threshold limit.
On the UP version, the measuring in-
puts are not polarity-sensitive. If the
measuring current reaches the re-
sponse value I
on
, auxiliary contact 11-
14 changes over and the LED lights. If
the measured current falls below the
hysteresis value I
off
and automatic re-
set is selected, the auxiliary contact
changes over again and the LED goes
out. The unit is ready for operation
again. If faults are latched, the unit will
not be ready for operation again until
an external reset button is operated or
the supply voltage has been switched
off and then on again.
Internal wiring diagram
S1IM
G1
K1
12 14
11
~
=
A2
(-)
A1
(+)
B
U
Y1 Y2 Y3
2 A E0.1 A
Messeingänge
Hilfskontakt
Auxiliary contact
Inverseur
Contacto auxiliar
Contatto ausiliario
Hulpcontact
Ruhe-/Arbeitsstrom
Normally energised/de-energised
Mode retombée/excitation
Corriente de trabajo/reposo
Corrente di riposo/di lavoro
Rust-/Arbeidsstroom
speichernd/nicht speichernd
latching/non-latching
mémorisation/sans mémorisation
acumuladora/no acumuladora
con memorizzazione/senza memorizazzione
handm./autom. reset
Ruhe-/Arbeitsstrom
Normally energised/
de-energised
Mode retombée/
excitation
Corriente de
trabajo/reposo
Corrente di riposo/
di lavoro
Rust-/Arbeidsstroom
Speichern
Store
Enregistrer
Guardar
Memorizzazione
Handm./autom. reset
Measurement inputs
Entrées de mesure
Entradas de medición
Ingressi di misura
Meetingangen