PNOZ XV1P } Safety relays Operating Manual 20596-EN-07
Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Source code from third-party manufacturers or open source software has been used for some components. The relevant licence information is available on the Internet on the Pilz homepage.
Contents Introduction Validity of documentation Using the documentation Definition of symbols 5 5 5 5 Safety Intended use Safety regulations Safety assessment Use of qualified personnel Warranty and liability Disposal For your safety 6 6 6 6 7 7 7 7 Unit features 8 Safety features 8 Block diagram/terminal configuration 8 Function Description Operating modes Timing diagram 9 9 10 Installation 10 Wiring 11 Preparing for operation 12 Operation Status indicators 14 14 Faults – Interference
Contents Remove plug-in terminals 28 Order reference 28 EC declaration of conformity 28 Operating Manual PNOZ XV1P 20596-EN-07 4
PNOZ XV1P Introduction Validity of documentation This documentation is valid for the product PNOZ XV1P. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product. Using the documentation This document is intended for instruction. Only install and commission the product if you have read and understood this document. The document should be retained for future reference.
PNOZ XV1P INFORMATION This gives advice on applications and provides information on special features. Safety Intended use The safety relay PNOZ XV1P provides a safety-related interruption of a safety circuit.
PNOZ XV1P Use of qualified personnel The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by competent persons. A competent person is someone who, because of their training, experience and current professional activity, has the specialist knowledge required to test, assess and operate the work equipment, devices, systems, plant and machinery in accordance with the general standards and guidelines for safety technology.
PNOZ XV1P Unit features } } Positive-guided relay outputs: – 2 safety contacts (N/O), instantaneous – 1 safety contact (N/O), delay-on de-energisation Connection options for: – E-STOP pushbuttons – Safety gate limit switches – Start buttons – Light grids and safety switches with detection of shorts across contacts } Selectable delay time } LED display for: – Supply voltage – Switch status of the safety contacts } Plug-in connection terminals (either spring-loaded terminal or screw ter
PNOZ XV1P Function Description The safety relay PNOZ XV1P provides a safety-oriented interruption of a safety circuit. When the supply voltage is applied via the E-STOP pushbutton, the “PWR” LED is lit. The unit is ready for operation when the start circuit S11-S14 is closed. } } Input circuit is closed (e.g. E-STOP pushbutton not operated): – The LEDs "CH.1/2" and "CH.1/2[t]" are lit. – Safety contacts 13-14, 23-24 and 37-38 are closed, the unit is active. Input circuit is opened (e.g.
PNOZ XV1P Timing diagram [1] [2] Output safe Output safe delay v v v v Legend } Power: Supply voltage } Start: Start circuit } Input: Input circuit } Output safe: Safety contacts, instantaneous } Output safe delay: Delayed safety contact } [1]: Automatic start } [2]: Monitored start } t1: Switch-on delay } t2: Delay-on de-energisation } t3: Waiting period with a monitored start } t4: Recovery time } tv: Delay time NOTICE At the latest, the delay-on de-energisation safety conta
PNOZ XV1P Wiring Please note: } Information given in the "Technical details [ } Outputs 13-14, 23-24 are instantaneous safety contacts, output 37-38 is a delay-on deenergisation safety contact. } To prevent contact welding, a fuse should be connected before the output contacts (see Technical details [ 16]). } Calculation of the max. cable runs lmax in the input circuit: Imax = 16]" must be followed. Rlmax Rl / km Rlmax = max.
PNOZ XV1P Preparing for operation Supply voltage AC Input circuit DC Single-channel E-STOP A1 L+ A2 L- Dual-channel S1 S1 S11 without detection of shorts across contacts S11 S21 S12 S21 S22 S32 S22 S12 S32 E-STOP S1 S12 with detection of shorts across contacts S11 S21 S12 S22 S32 Safety gate without detection of shorts across contacts S1 S11 S21 S12 S22 S32 S11 S21 S22 S1 S2 S12 S32 Safety gate with detection of shorts across contacts Light guard or safety switch, det
PNOZ XV1P NOTICE Operation with a light guard or safety switch It must not be possible to switch off the supply voltage for the PNOZ XV1P separately from the supply voltage for the light guard or safety switch. E-STOP wiring, safety gate without start-up test Start circuit Automatic start Safety gate with start-up test S11 S14 S1 S2 S11 S14 Simultaneity S1 and S2: max. 1 s Monitored start NOTICE In the event of an automatic start: The unit starts up automatically when the safeguard is reset, e.g.
PNOZ XV1P INFORMATION With automatic start, S33 and S34 must not be linked; with monitored start, S11 and S14 must not be linked. Operation NOTICE Check each safety function – after initial commissioning and after each change of the machine/ plant – for SIL CL 3/PL e at least 1x per month, for SIL CL 2/PL d at least 1x per year Follow the instructions below: – Activate the safety function and check whether all the used safety contacts open. – Prepare for operation again and start the unit.
PNOZ XV1P Faults – Interference } Earth fault: The supply voltage fails and the safety contacts open. Once the cause of the respective fault has been rectified and the supply voltage is switched off for approx. 1 minute, the unit is ready for operation again. } Contact malfunctions: If the contacts have welded, reactivation will not be possible after the input circuit has opened. } LED "PWR" does not light: Short circuit or no supply voltage.
PNOZ XV1P Technical details Order no. 777601 – 777602 See below for more order numbers General 777601 CCC, CE, EAC (Eurasian), TÜV, Approvals cULus Listed Electrical data 777601 Supply voltage Voltage 24 V Kind DC Voltage tolerance -15 %/+10 % Output of external power supply (DC) 3,5 W Residual ripple DC 20 % Duty cycle 100 % Max.
PNOZ XV1P Relay outputs Utilisation category of safety contacts AC1 at Min. current Max. current Max. power DC1 at Min. current Max. current Max. power Utilisation category of safety contacts delayed AC1 at Min. current Max. current Max. power DC1 at Min. current Max. current Max. power Utilisation category In accordance with the standard Utilisation category of safety contacts AC15 at Max. current DC13 (6 cycles/min) at Max. current Utilisation category of safety contacts delayed AC15 at Max.
PNOZ XV1P Relay outputs External contact fuse protection, safety contacts In accordance with the standard Max. melting integral Blow-out fuse, quick Blow-out fuse, slow Blow-out fuse, gG Circuit breaker 24V AC/DC, characteristic B/C External contact fuse protection, delayed safety contacts Max.
PNOZ XV1P Times Time accuracy Repetition accuracy Waiting period with a monitored start Min. start pulse duration with a monitored start Supply interruption before de-energisation Simultaneity, channel 1 and 2 max.
PNOZ XV1P Mechanical data Conductor cross section with screw terminals 1 core flexible 2 core with the same cross section, flexible with crimp connectors, no plastic sleeve 2 core with the same cross section, flexible without crimp connectors or with TWIN crimp connectors Torque setting with screw terminals Dimensions Height Width Depth Weight 777601 777602 0,25 - 2,5 mm², 24 - 12 AWG 0,25 - 2,5 mm², 24 - 12 AWG 0,25 - 1 mm², 24 - 16 AWG 0,25 - 1 mm², 24 - 16 AWG 0,2 - 1,5 mm², 24 - 16 AWG 0,5 Nm 0
PNOZ XV1P Inputs Current at Input circuit DC Start circuit DC Feedback loop DC Max. overall cable resistance Rlmax Single-channel at UB DC Dual-channel without detection of shorts across contacts at UB DC Dual-channel with detection of shorts across contacts at UB DC Relay outputs Number of output contacts Safety contacts (N/O), instantaneous Safety contacts (N/O), delayed Max. short circuit current IK Utilisation category In accordance with the standard Utilisation category of safety contacts AC1 at Min.
PNOZ XV1P Relay outputs Utilisation category of safety contacts AC15 at Max. current DC13 (6 cycles/min) at Max. current Utilisation category of safety contacts delayed AC15 at Max. current DC13 (6 cycles/min) at Max. current Utilisation category in accordance with UL Voltage With current Pilot Duty External contact fuse protection, safety contacts In accordance with the standard Max.
PNOZ XV1P Times Switch-on delay With automatic start typ. With automatic start max. With automatic start after power on typ. With automatic start after power on max. With monitored start typ. With monitored start max. Delay-on de-energisation With E-STOP typ. With E-STOP max. With power failure typ. With power failure max. Recovery time at max. switching frequency 1/s After E-STOP After power failure – Time accuracy Repetition accuracy Waiting period with a monitored start Min.
PNOZ XV1P Environmental data Airgap creepage In accordance with the standard Overvoltage category Pollution degree Rated insulation voltage Rated impulse withstand voltage Protection type Mounting area (e.g.
PNOZ XV1P Safety characteristic data NOTICE You must comply with the safety-related characteristic data in order to achieve the required safety level for your plant/machine. Operating mode EN ISO 13849-1: 2008 EN ISO 13849-1: 2008 PL Category Safety contacts, instantaneous PL e Safety contacts, delayed <30 PL d s Safety contacts, delayed ≥30 PL c s EN 62061 EN 62061 IEC 61511 IEC 61511 SIL CL PFHD [1/h] SIL PFD EN ISO 13849-1: 2008 TM [year] Cat.
PNOZ XV1P Service life graph The service life graphs indicate the number of cycles from which failures due to wear must be expected. The wear is mainly caused by the electrical load; the mechanical load is negligible. Cycles x 1000 Service life graph: Safety contacts (N/O), instantaneous Switching current (A) Example } Inductive load: 0.
PNOZ XV1P Cycles x 1000 Service life graph: Safety contact (N/O), delay-on de-energisation Switching current (A) Example } Inductive load: 0.2 A, } Utilisation category: AC15 } Contact service life: 900 000 cycles Provided the application to be implemented requires fewer than 900 000 cycles, the PFH value (see Technical details) can be used in the calculation. To increase the service life, sufficient spark suppression must be provided on all output contacts.
PNOZ XV1P Remove plug-in terminals Procedure: Insert the screwdriver into the housing recess behind the terminal and lever the terminal out. Do not remove the terminals by pulling the cables! Order reference Product type Features Connection type Order no.
Technical support is available from Pilz round the clock.