User Manual

PNOZ 11
Operating Manual PNOZ 11
19147-EN-05
8
Function Description
The safety relay PNOZ 11 provides a safety-oriented interruption of a safety circuit. When
supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation when the
feedback loop Y1-Y2 and the start circuit S33-S34 are closed. The "START" LED is lit.
} Input circuit is closed (e.g. E-STOP pushbutton not operated):
The LEDs "CH.1IN" and "CH.2 IN" are lit.
The "START" LED goes out.
Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54, 63-64 and 73-74 are closed,
auxiliary contact 81-82 is opened. The unit is active.
The LEDs "CH.1" and "CH.2" are lit.
A high signal is present at the semiconductor output switch state Y32.
} Input circuit is opened (e.g. E-STOP pushbutton operated):
The LEDs "CH.1IN" and "CH.2 IN" go out.
Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54, 63-64 and 73-74 are opened re-
dundantly, auxiliary contact 81-82 is closed.
The LEDs "CH.1" and "CH.2" go out.
A low signal is present at the semiconductor output switch state Y32.
Semiconductor output supply voltage Y35
} A high signal is present at semi-conductor output Y35 if the supply voltage is present
and the internal fuse has not blown.
Operating modes
} Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
} Dual-channel operation with detection of shorts across contacts: Redundant input cir-
cuit, PNOZ 11 detects
earth faults in the start and input circuit,
short circuits in the input circuit,
shorts across contacts in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start: Unit is active once the input circuit and the start circuit are closed.
} Monitored start: Unit is active once
the input circuit is closed and then the start circuit is closed and opened again.
the start circuit is closed and then opened again once the input circuit is closed.
} Increase in the number of available contacts by connecting contact expander modules
or external contactors/relays.