User Manual
PNOZ 11
Operating Manual PNOZ 11
19147-EN-05
24
Conventional thermal current
while loading several contacts
774085 774086
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 8 A 8 A
Conv. therm. current with 3 con-
tacts 8 A 8 A
Conv. therm. current with 4 con-
tacts 6,9 A 6,9 A
Conv. therm. current with 5 con-
tacts 6,2 A 6,2 A
Conv. therm. current with 6 con-
tacts 5,6 A 5,6 A
Conv. therm. current with 7 con-
tacts 5,2 A 5,2 A
Times 774085 774086
Switch-on delay
With automatic start typ. 330 ms 330 ms
With automatic start max. 450 ms 450 ms
With automatic start after power
on typ. 330 ms 330 ms
With automatic start after power
on max. 480 ms 480 ms
With manual start typ. 335 ms 335 ms
With manual start max. 450 ms 450 ms
With monitored start typ. 330 ms 330 ms
With monitored start max. 450 ms 450 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms
With E-STOP max. 30 ms 30 ms
With power failure typ. 40 ms 40 ms
With power failure max. 60 ms 60 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 100 ms 100 ms
Min. start pulse duration with a
monitored start 30 ms 30 ms
Supply interruption before de-ener-
gisation 10 ms 10 ms
Simultaneity, channel 1 and 2 max. ∞ ∞
Environmental data 774085 774086
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C