User Manual
PNOZ 11
Operating Manual PNOZ 11
19147-EN-05
22
Relay outputs 774085 774086
Number of output contacts
Safety contacts (N/O), instant-
aneous 7 7
Auxiliary contacts (N/C) 1 1
Max. short circuit current IK 1 kA 1 kA
Utilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1
Utilisation category of safety con-
tacts
AC1 at 400 V 400 V
Min. current 0,01 A 0,01 A
Max. current 5 A 5 A
Max. power 2000 VA 2000 VA
AC1 at 240 V 240 V
Min. current 0,01 A 0,01 A
Max. current 8 A 8 A
Max. power 2000 VA 2000 VA
DC1 at 24 V 24 V
Min. current 0,01 A 0,01 A
Max. current 8 A 8 A
Max. power 200 W 200 W
Utilisation category of auxiliary con-
tacts
AC1 at 240 V 240 V
Min. current 0,01 A 0,01 A
Max. current 8 A 8 A
Max. power 2000 VA 2000 VA
DC1 at 24 V 24 V
Min. current 0,01 A 0,01 A
Max. current 8 A 8 A
Max. power 200 W 200 W
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at 230 V 230 V
Max. current 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 7 A 7 A
Utilisation category of auxiliary con-
tacts
AC15 at 230 V 230 V
Max. current 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 7 A 7 A