User Manual

PNOZ X7
Operating Manual PNOZ X7
19692-EN-05
19
Relay outputs 774055 774056 774057
Utilisation category
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 4 A 4 A 4 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 4 A 4 A 4 A
Utilisation category in ac-
cordance with UL
Voltage 240 V AC G. P. 240 V AC G. P. 240 V AC G. P.
With current 4 A 4 A 4 A
Voltage 24 V DC Resistive 24 V DC Resistive 24 V DC Resistive
With current 4 A 4 A 4 A
Pilot Duty C300, R300 C300, R300 C300, R300
External contact fuse pro-
tection, safety contacts
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 4 A 4 A 4 A
Blow-out fuse, slow 4 A 4 A 4 A
Blow-out fuse, gG 4 A 4 A 4 A
Circuit breaker 24V
AC/DC, characteristic
B/C 4 A 4 A 4 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal
current while loading
several contacts
774055 774056 774057
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 4 A 4 A 4 A
Conv. therm. current
with 2 contacts 3 A 3 A 3 A
Times 774055 774056 774057
Switch-on delay
With automatic start
typ. 230 ms 230 ms 230 ms
With automatic start
max. 700 ms 700 ms 700 ms
With automatic start
after power on typ. 230 ms 230 ms 230 ms
With automatic start
after power on max. 700 ms 700 ms 700 ms
With manual start typ. 140 ms 140 ms 140 ms
With manual start max. 700 ms 700 ms 700 ms