Datasheet
PNOZmulti 2 products
Base units
PNOZ m B0
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
672
Semiconductor outputs
Redundant output
K2
L-
O0 (O2)
O1 (O3)
K1
L-
Single output
K3
L-
K4
O0 (O2)
O1 ( O3)
K1
L-
K2
Single output with advanced fault
detection*
K1
L+
L-
K2
O0 (O2)
i0
*Two loads may be connected to each safety output with advanced fault detection, even on
applications in accordance with EN IEC 62061, SIL CL 3. Prerequisite: Feedback loop is
connected, shorts across contacts and external power sources are excluded (e.g. through
separate multicore cables). Please note that, in the event of an error in the feedback loop,
the safety system switches to a safe condition and shuts down all the outputs.
Feedback loop Redundant output
Contacts from external contactors
K1
L+
L-
K2
O0 (O2)
O1 (O3)
IM0