Datasheet

PNOZmulti products
Base units
PNOZ m1p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
103
Test pulse outputs 773100 773103 773104 773105
Number of test pulse
outputs
4 4 4 4
Voltage 24 V 24 V 24 V 24 V
Current 0,5 A 0,5 A 0,5 A 0,5 A
Max. duration of off
time during self test
5 ms 5 ms 5 ms 5 ms
Short circuit-proof yes yes yes yes
Potential isolation No No No No
Relay outputs 773100 773103 773104 773105
Utilisation category
In accordance
with the standard
EN 60947-4-1 EN 60947-4-1 EN 60947-4-1 EN 60947-4-1
Utilisation category
of safety contacts
AC1 at 240 V 240 V 240 V 240 V
Max. current 6,0 A 6,0 A 6,0 A 6,0 A
Max. power 1440 VA 1440 VA 1440 VA 1440 VA
DC1 at 24 V 24 V 24 V 24 V
Max. current 6,0 A 6,0 A 6,0 A 6,0 A
Max. power 144 W 144 W 144 W 144 W
Safety contacts,
AC1 at 240 V 240 V
Max. current 4 A 4 A
Max. power 960 W 960 W
Safety contacts,
DC 1 at 24 V 24 V
Max. current 4 A 4 A
Max. power 96 W 96 W
Utilisation category
In accordance
with the standard
EN 60947-5-1 EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category
of safety contacts
AC15 at 230 V 230 V 230 V 230 V
Max. current 3,0 A 3,0 A 3,0 A 3,0 A
Max. power 690 W 690 W 690 W 690 W
DC13 (6 cycles/
min) at 24 V 24 V 24 V 24 V
Max. current 3,0 A 3,0 A 3,0 A 3,0 A
Max. power 72 W 72 W 72 W 72 W