Function description
Functions
The virtual inputs and outputs that are to be transferred via the fieldbus CC-Link are selec-
ted and configured in the PNOZmulti Configurator. The base unit and the fieldbus module
PNOZ m ES CC-Link are connected via a jumper. After the supply voltage is switched on or
the PNOZmulti control system is reset, the fieldbus module PNOZ m ES CC-Link is con-
figured and started automatically.
LEDs indicate the status of the fieldbus module CC-Link.
The configuration is described in detail in the PNOZmulti Configurator's online help.
To send and receive data three stations have to be created in CC-Link master.
Input and output data
Virtual inputs and outputs can be requested or set directly via the following addresses. The
implementation to the names of the inputs and outputs in PNOZmulti 2 is performed as in
the table listed below.
The data is structured as follows:
} Input area
Inputs on PNOZmulti Configurator: i00 .. i127
Input data CC-Link: RYmn.. RY(m+50)n, RWw l .. RWw l+2
with l = address can be set as required on the master side (word address)
with m = address can be set as required on the master side (Bit address)
with n = 0 .. F (Bit number)
Example: (with m=100) i23 -> n = 7 -> RY117
Bit addressed input data i00 - i87
n F E D C B A 9 8 7 6 5 4 3 2 1 0
RY m n i15 i14 i13 i12 i11 i10 i09 i08 i07 i06 i05 i04 i03 i02 i01 i00
RY(m+10)n i31 i30 i29 i28 i27 i26 i25 i24 i23 i22 i21 i20 i19 i18 i17 i16
RY(m+20)n i47 i46 i45 i44 i43 i42 i41 i40 i39 i38 i37 i36 i35 i34 i33 i32
RY(m+30)n i63 i62 i61 i60 i59 i58 i57 i56 i55 i54 i53 i52 i51 i50 i49 i48
RY(m+40)n i79 i78 i77 i76 i75 i74 i73 i72 i71 i70 i69 i68 i67 i66 i65 i64
RY(m+50)n i87 i86 i85 i84 i83 i82 i81 i80