} Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
Connecting the supply voltage
Connect the supply voltage to the fieldbus module:
} 24 V terminal: + 24 VDC
} 0 V terminal: 0 V
} Protect the supply voltage as follows:
– Circuit breaker, characteristic C - 6 A
or
– Blow-out fuse, slow, 6A
Interface assignment
RJ45 socket
8-pin
PIN Standard
8 1
1 TD+ (Transmit+)
2 TD- (Transmit-)
3 RD+ (Receive+)
4 n.c.
5 n.c.
6 RD- (Receive-)
7 n.c.
8 n.c.
n.c.: Not connected
Preparing for operation
Set IP address
There are two options:
} Automatic assignment of the IP address with the Dynamic Host Configuration Protocol
(DHCP)
} Assignment of the IP address by the IOcontroller before system startup based on the
unique unit name.