Function description
Operation
The virtual inputs and outputs that are to be transferred via PROFINET are selected and
configured in the PNOZmulti Configurator. The base unit and the expansion module PNOZ
m ES Profinet are connected via a jumper.
After the supply voltage is switched on or the PNOZmulti 2 is reset, the expansion module
PNOZ m ES Profinet is configured and started automatically.
LEDs indicate the status of the fieldbus module PROFINET.
The configuration is described in detail in the PNOZmulti Configurator's online help.
Data access
The data is structured as follows:
} Virtual data
Input area PNOZ m ES Profinet
The values for the inputs are set in the Master as an output and transferred to the
PNOZmulti 2.
Output area PNOZ m ES Profinet
The outputs are configured in the PNOZmulti Configurator and transferred to the
Master.
} Status of LEDs:
Bits 0 … 4: Status of LEDs on the PNOZmulti 2
Bit 0: OFAULT
Bit 1: IFAULT
Bit 2: FAULT
Bit 3: DIAG
Bit 4: RUN
} Data exchange is displayed in Bit 5.
} Polling the payload data: 2 Bytes with the table number and segment number are sent
by the Master for access to the payload data table (15 Bytes are returned to the Mas-
ter).
Detailed information on data exchange (tables, segments) is available in the document
"Communication Interfaces" in the section entitled "Fieldbus modules".