Datasheet
PNOZmulti products
Base units
PNOZ m0p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
87
Input
Cascad. in-
puts
–
PL e Cat. 4 SIL CL 3 3,10E-10 20
Output
SC outputs 1-channel PL d Cat. 2 SIL CL 2 7,00E-09 20
SC outputs 2-channel PL e Cat. 4 SIL CL 3 8,60E-10 20
Cascad. out-
puts
– PL e Cat. 4 SIL CL 3 4,91E-10 20
Relay outputs 1-channel PL c Cat. 1 - 2,90E-08 20
Relay outputs 2-channel PL e Cat. 4 SIL CL 3 3,00E-10 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
The PFH value depends on the switching frequency and the load on the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switching frequency and the load, as the PFH value already considers the relay's
B10d value as well as the failure rates of the other components.