Datasheet

PNOZmulti 2 products
Fieldbus modules
PNOZ m ES EtherNet/IP
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
867
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
Connecting the supply voltage
Connect the supply voltage to the fieldbus module:
} 24 V terminal: + 24 VDC
} 0 V terminal: 0 V
} Protect the supply voltage as follows:
Circuit breaker, characteristic C - 6 A
or
Blow-out fuse, slow, 6A
Interface assignment
RJ45 socket
8-pin
PIN Standard
8 1
1 TD+ (Transmit+)
2 TD- (Transmit-)
3 RD+ (Receive+)
4 n.c.
5 n.c.
6 RD- (Receive-)
7 n.c.
8 n.c.
n.c.: Not connected
Set IP address
The IP address of the fieldbus module PNOZ m ES EtherNet/IP is set using the DIP switch
on the front.
} The first three bytes of the IP address are: 192.168.1.
} Subnet mask: 255.255.255.0.
} The last byte of the IP address is configured (value range: 1 ...255).
There are various options for setting the IP address.