Datasheet
PNOZmulti products
Base units
PNOZ m0p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
84
Times 773110 773113
Max. cycle time of the device 15 ms 15 ms
Max. processing time for data com-
munication
–
50 ms
Environmental data 773110 773113
Ambient temperature
In accordance with the standard EN 60068-2-14 EN 60068-2-14
Temperature range 0 - 60 °C 0 - 60 °C
Forced convection in control
cabinet off
55 °C 55 °C
Storage temperature
In accordance with the standard EN 60068-2-1/-2 EN 60068-2-1/-2
Temperature range -25 - 70 °C -25 - 70 °C
Climatic suitability
In accordance with the standard EN 60068-2-30, EN 60068-2-78 EN 60068-2-30, EN 60068-2-78
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during operation Not permitted Not permitted
EMC EN 61131-2 EN 61131-2
Vibration
In accordance with the standard EN 60068-2-6 EN 60068-2-6
Frequency 10,0 - 150,0 Hz 10,0 - 150,0 Hz
Acceleration 1g 1g
Shock stress
In accordance with the standard EN 60068-2-27 EN 60068-2-27
Acceleration 15g 15g
Duration 11 ms 11 ms
Max. operating height above sea
level
2000 m 2000 m
Airgap creepage
In accordance with the standard EN 61131-2 EN 61131-2
Overvoltage category III III
Pollution degree 2 2
Rated insulation voltage 250 V 250 V
Rated impulse withstand voltage 6,00 kV 6,00 kV
Protection type
In accordance with the standard EN 60529 EN 60529
Mounting area (e.g. control cab-
inet) IP54 IP54
Housing IP20 IP20
Terminals IP20 IP20
Potential isolation 773110 773113
Potential isolation between SC output and system voltage SC output and system voltage
Type of potential isolation Protective separation Protective separation