Datasheet
PNOZmulti 2 products
Fieldbus modules
PNOZ m ES Profibus
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
834
Installation
Dimensions in mm
101,4 (4,11“)
115,0 (4,53“)
22,5
(0,88“)
Commissioning
Wiring
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
} Information given in the Technical details [
837] must be followed.
} Use copper wire that can withstand 75°C.
} External measures must be used to connect the terminal
to the functional earth,
when the mounting rail is not connected to the functional earth.
} Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
Connecting the supply voltage
Connect the supply voltage to the fieldbus module:
} 24 V terminal: + 24 VDC
} 0 V terminal: 0 V
} Protect the supply voltage as follows:
– Circuit breaker, characteristic C - 6 A