Datasheet

PNOZmulti 2 products
Communication modules
PNOZ m ES ETH
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
820
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
} Information given in the Technical details [
820] must be followed.
} Use copper wire that can withstand 75°C.
Preparing for operation
Detection and activation of the Ethernet interface, depending on the USB interface on the
base unit:
} USB interface on the base unit not connected
If the USB interface on the base unit is not connected, the Ethernet interface will be de-
tected and activated by the base unit as soon as the communication module has been
connected to the base unit.
} USB interface on the base unit connected
If the USB interface on the base unit is already connected, the "Ethernet" interface will
first need to be selected on the base unit display to enable the Ethernet interface on the
base unit to be detected and activated (see operating manual for the base unit for de-
tails of the setting).
Tecnical details
General
Approvals CCC, CE, EAC (Eurasian), cULus Listed
Application range Standard
Module's device code 1202h
Electrical data
Supply voltage
for Module supply
internal Via base unit
Voltage 3,3 V
Kind DC
Voltage tolerance -2 %/+2 %
Current consumption 295 mA
Power consumption 1,0 W
Status indicator LED
Ethernet interface
Number 2
IP address (automatically off) 169.254.60.1