Datasheet

PNOZmulti 2 products
Link modules
PNOZ m EF PDP Link
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
807
Installation
Dimensions in mm
22,5
(0.88")
Commissioning
Wiring
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
} Information given in the Technical details [
811] must be followed.
} Use copper wire that can withstand 75°C.
} External measures must be used to connect the FE terminal to the function earth (e.g.
mounting rail).
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
} 2 connection terminals are available for each of the supply connections 24 V and 0 V.
This means that the supply voltage can be looped through several connections. The
current at each terminal may not exceed 3 A.
} Please refer to the technical details for information on the maximum cable length.
Please also read the section entitled "Voltage drop".
} Shielded cable must be used from a cable length of 30 m.
} Pilz pre-assembled cable can be used to connect the decentralised modules (see order
reference).
} The plug-in connection terminals are either designed as cage clamp terminals or screw
terminals (see order reference).