PNOZ m EF Multi Link
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
799
Commissioning
Wiring
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
} Information given in the Technical details [
800] must be followed.
} Use copper wire that can withstand 75°C.
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
} 2 connection terminals are available for each of the supply connections 24 V and 0 V.
This means that the supply voltage can be looped through several connections. The
current at each terminal may not exceed 3 A.
} The max. cable length between two link modules on a connection with one link module
– PNOZ ml1p <V2.0: 100 m
– PNOZ ml1p from V2.0, PNOZ mml1p, PNOZ m EF Multi Link: 1000 m
} Connect the inputs and outputs from two link modules with 4-core shielded cable. The
cables must be twisted in pairs (see "Preparing for operation").
} Note the crossover cabling, e.g. CA+ with CB+.
} The cables must be classified into a minimum of Category 5 in accordance with ISO/
IEC 11801.
Connection
RJ45 socket
8-pin
PIN Layout
8 1
1 CA+
2 CA-
3 CB+
4 n.c.
5 n.c.
6 CB-
7 n.c.
8 n.c.
Shield CGround