Datasheet
PNOZmulti 2 products
Motion monitoring modules
PNOZ m EF 1MM
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
760
EMC-compliant wiring for connecting 2 proximity switches
PNOZ m EF 2MM
S12
To avoid EMC interference we recommend that the shield on the sensor cables or the
housing of the shielded junction box is only connected to earth at a single point:
A or B or C or D or E
Conductor loops outside the shield must be avoided.
If a shielded junction box is not used, the shield must run continuously from the sensor to
the evaluation device.
Technical details
General
Approvals BG, CCC, CE, EAC (Eurasian), TÜV, cULus Listed
Application range Failsafe
Module's device code 00E3h
Electrical data
Supply voltage
for Module supply
internal Via base unit
Voltage 24 V
Kind DC
Current consumption 90 mA
Power consumption 2 W
Max. power dissipation of module 2,2 W
Status indicator LED