Datasheet

PNOZmulti 2 products
Base units
PNOZ m B1
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
686
Detection of shorts across contacts
4 test pulse outputs that use different test pulses (test pulse0 (T0) ... test pulse3 (T3)) are
available for detecting shorts between the inputs.
Shorts between inputs are detected if the inputs are connected to different test pulses (test
pulse 0 ... test pulse 3).
Pulsing of test pulse outputs T0 ... T3 (typical times):
4 ms
T0
T1
T2
T3
4 ms
6 ms
4 ms
6 ms
4 ms
6 ms
4 ms
4 ms
6 ms
4 ms
6 ms
4 ms
6 ms
200 ms