Datasheet
PNOZmulti 2 products
Base units
PNOZ m B1
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
686
Detection of shorts across contacts
4 test pulse outputs that use different test pulses (test pulse0 (T0) ... test pulse3 (T3)) are
available for detecting shorts between the inputs.
Shorts between inputs are detected if the inputs are connected to different test pulses (test
pulse 0 ... test pulse 3).
Pulsing of test pulse outputs T0 ... T3 (typical times):
4 ms
T0
T1
T2
T3
4 ms
6 ms
4 ms
6 ms
4 ms
6 ms
4 ms
4 ms
6 ms
4 ms
6 ms
4 ms
6 ms
200 ms