Datasheet

PNOZmulti Mini products
Fieldbus modules
PNOZ mmc12p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
656
LEDs indicate the status of the fieldbus module Ethernet POWERLINK.
The configuration is described in detail in the PNOZmulti Configurator's online help.
Input and output data
The data is structured as follows:
} Input area
The inputs are defined in the Managing Node and transferred to the PNOZmulti. Each
input has a number, e.g. input bit 4 of SDO 2100:02 has the number i12.
Virtual inputs
PNOZmulti Configur-
ator
I0 … I7 I8 … I15 I16 … I23
Ethernet POWER-
LINK
SDO 2100:01:
Bit 0 … 7
SDO 2100:02:
Bit 0 … 7
SDO 2100:03:
Bit 0 … 7
} Output range
The outputs are defined in the PNOZmulti Configurator. Each output that is used is
given a number there, e.g. o0, o5... The state of output o0 is stored in Bit 0 of SDO
2000:01.
Virtual outputs
PNOZmulti Configur-
ator
O0 … O7 O8 … O15 O16 … O23
Ethernet POWER-
LINK
SDO 2000:01:
Bit 0 … 7
SDO 2000:02:
Bit 0 … 7
SDO 2000:03:
Bit 0 … 7
Detailed information on data exchange is available in the document "Communication Inter-
faces" in the section entitled "Fieldbus modules".
The number of virtual inputs and outputs can be extended to 128 (see document "Commu-
nication Interfaces" in the section entitled "Fieldbus modules")