Datasheet
PNOZmulti Mini products
Fieldbus modules
PNOZ mmc11p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
648
Installation
Dimensions in mm
115,0 (4,53“)
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
It is possible to define which inputs and outputs on the safety system will communicate with
EtherCAT.
Please note:
} Information given in the "Technical details" must be followed.
} Use copper wire that can withstand 75 °C.
} External measures must be used to connect the
terminal to the function earth (e.g.
mounting rail).
Please note the following when connecting to EtherCAT:
} The following minimum requirements of the connection cable and connector must be
met:
– Only use standard industrial Ethernet cable and connectors.
– Only use double-shielded twisted pair cable and shielded RJ45 connectors (indus-
trial connectors).
– 100BaseTX cable in accordance with the Ethernet standard (min. Category 5)
} Measures to protect against interference:
Ensure the requirements for the industrial use of EtherCAT are met, as stated in the In-
stallation Manual published by the User Group.