Interface configuration
Serial interface
RS232
Standard
TxD RxD GND
TxD (Transmit)
RxD (Receive)
GND (Ground)
Preparing for operation
The serial interface RS 232 is activated and detected depending on the USB interface on
the base unit:
} USB interface on the base unit not connected
In this case, the serial interface RS 232 will be detected and activated by the base unit
as soon as the communication module has been connected to the base unit.
} USB interface on the base unit connected
If the USB interface on the base unit is already connected, the "External" interface will
first need to be selected on the base unit display to enable the serial interface RS 232
on the base unit to be detected and activated (see operating manual for the base unit
for details of the setting).
Technical details
General
Approvals CCC, CE, EAC (Eurasian), KCC, cULus Listed
Electrical data
Supply voltage
for Module supply
internal Via base unit
Voltage 3,3 V
Kind DC
Voltage tolerance -2 %/+2 %
Power consumption 30,0 mW
Status indicator LED
Fieldbus interface
Galvanic isolation No
Serial interface
Number of RS232 interfaces 1