Datasheet
PNOZmulti Mini products
Base units
PNOZ mm0.1p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
535
Start circuit Input circuit without detection of
shorts across contacts
Input circuit with detection of
shorts across contacts
I5
S3
L+
I5
T0M20
S3
Redundant output
K2
L-
O0 (O2)
O1 (O3)
K1
L-
Single output
K3
L-
K4
O0 (O2)
O1 ( O3)
K1
L-
K2
Single output with advanced fault
detection*
K1
L+
L-
K2
O0 (O2)
IM0
*Two loads may be connected to each safety output with advanced fault detection, even on
applications in accordance with EN IEC 62061, SIL CL 3. Prerequisite: Feedback loop is
connected, shorts across contacts and external power sources are excluded (e.g. through
separate multicore cables). Please note that, in the event of an error in the feedback loop,
the safety system switches to a safe condition and shuts down all the outputs.