Safety characteristic data
Unit Operating
mode
EN ISO
13849-1: 2008
PL
EN ISO
13849-1: 2008
Category
EN 62061
SIL CL
EN 62061
PFH
D
[1/h]
EN ISO
13849-1: 2008
T
M
[year]
Logic
CPU 2-channel PL e Cat. 4 SIL CL 3 1,54E-09 20
Input
SC inputs 1-channel PL d Cat. 2 SIL CL 2 3,95E-09 20
SC inputs 2-channel PL e Cat. 4 SIL CL 3 4,61E-10 20
SC inputs 1-ch., pulsed
light barrier
PL e Cat. 4 SIL CL 3 3,95E-10 20
Output
SC outputs 1-channel
with ad-
vanced fault
detection
PL e Cat. 4 SIL CL 3 7,65E-10 20
SC outputs 1-channel PL d Cat. 2 SIL CL 2 8,90E-10 20
SC outputs 2-channel PL e Cat. 4 SIL CL 3 7,86E-10 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.