Datasheet

Basics
System expansion
Connection of multiple PNOZmulti systems
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
50
Example: Connecting 5 base units PNOZmulti
The maximum reaction time t
ReactionMax
includes the following times:
} Based max. input delay PNOZ mm0.1p (Base 1): 4ms
} Data transfer time of the connection at the PNOZ mml1p (Base 1): 35ms
} Max. input delay PNOZ mml1p (Base 2): 0ms
} Data transfer time of the connection at the PNOZ mml1p (Base 2): 35ms
} Max. input delay PNOZ mml1p (Base 2): 0ms
} Data transfer time of the connection at the PNOZ ml1p (Base 4): 35ms
} Max. input delay PNOZ m EF Multi Link (Base 5): 0ms
} Max. processing time PNOZ m B0 (Base 5): 30ms
} Max. switch-off delay at the output PNOZ mB0 (Base 5): 1ms
Base 3Base 1 Base 2
Base 5 Base 4