Datasheet

PNOZmulti products
Fieldbus modules
PNOZ mc12p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
489
Input and output data
The data is structured as follows:
} Input area
The inputs are defined in the Managing Node and transferred to the PNOZmulti. Each
input has a number, e.g. input bit 4 of SDO 2100:02 has the number i12.
Virtual inputs
PNOZmulti Configur-
ator
I0 … I7 I8 … I15 I16 … I23
Ethernet POWER-
LINK
SDO 2100:01:
Bit 0 … 7
SDO 2100:02:
Bit 0 … 7
SDO 2100:03:
Bit 0 … 7
} Output range
The outputs are defined in the PNOZmulti Configurator. Each output that is used is
given a number there, e.g. o0, o5... The state of output o0 is stored in Bit 0 of SDO
2000:01.
Virtual outputs
PNOZmulti Configur-
ator
O0 … O7 O8 … O15 O16 … O23
Ethernet POWER-
LINK
SDO 2000:01:
Bit 0 … 7
SDO 2000:02:
Bit 0 … 7
SDO 2000:03:
Bit 0 … 7
Detailed information on data exchange is available in the document "Communication Inter-
faces" in the section entitled "Fieldbus modules".
The number of virtual inputs and outputs can be extended to 128 (see document "Commu-
nication Interfaces" in the section entitled "Fieldbus modules")
Block diagram
Base unit
Ethernet POWERLINK