} The unit name on the Ethernet subnet must be unique. It must comply with the DNS
conventions:
– Max. 127 characters (letters, numbers, hyphen or period)
– Max. 63 characters between two periods
} The following characters are invalid: ä ö ü ( ) _ / space
} The unit name may not
– Begin or end with the "-" character.
– Have the form n.n.n.n (n = 0 ... 999).
– Start with the sequence "port-xyz-" (x, y, z = 0 ... 9).
Install GSD file
Install the GSD file. The GSD file is available on the Internet at www.pilz.de.
Set IP address
There are two options:
} Automatic assignment of the IP address with the Dynamic Host Configuration Protocol
(DHCP)
} Assignment of the IP address by the IOcontroller before system startup based on the
unique unit name.
Connecting the supply voltage
Connect the supply voltage to the base unit:
} Terminal 24 V and A1 (+): + 24VDC
} Terminal 0 V and A2 (-): 0 V