Datasheet
PNOZmulti products
Fieldbus modules
PNOZ mc8p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
465
} The power supply must meet the regulations for extra low voltages with protective sep-
aration.
Connecting the supply voltage
Connect the supply voltage to the base unit:
} Terminal 24 V and A1 (+): + 24VDC
} Terminal 0 V and A2 (-): 0 V
Interface assignment
RJ45 socket
8-pin
PIN Standard
8 1
1 TD+ (Transmit+)
2 TD- (Transmit-)
3 RD+ (Receive+)
4 n.c.
5 n.c.
6 RD- (Receive-)
7 n.c.
8 n.c.
n.c.: Not connected
Set IP address
The IP address of the fieldbus module PNOZ mc8p is set using the DIP switch on the front.
} The first three bytes of the IP address are: 192.168.1.
} Subnet mask: 255.255.255.0.
} The last byte of the IP address is configured (value range: 1 ...255).
Example: DIP switch: 00010100 (20 decimal)
(MSB) (LSB)
1 2 3 4 5 6 7 8
ON
IP address: 192.168.0.20