Datasheet

PNOZmulti products
Fieldbus modules
PNOZ mc8p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
464
Installation
Dimensions in mm
94 (3.70")
22,5
(0.88")
114 (4.49")
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator. It is possible to
define which inputs and outputs on the safety system will communicate with EtherNet/IP,
Modbus TCP.
Please note:
} Information given in the "Technical details [
467]" must be followed.
} Use copper wiring with a temperature stability of 75 °C.
Please note the following when connecting to EtherNet/IP, Modbus TCP:
} The following minimum requirements of the connection cable and connector must be
met:
Only use standard industrial Ethernet cable and connectors.
Only use double-shielded twisted pair cable and shielded RJ45 connectors (indus-
trial connectors).
100BaseTX cable in accordance with the Ethernet standard (min. Category 5)
} Measures to protect against interference:
Ensure the requirements for the industrial use of EtherNet/IP, Modbus TCP are met, as
stated in the Installation Manual published by the User Group.
} Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.