Datasheet
PNOZmulti products
Fieldbus modules
PNOZ mc8p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
462
Data exchange
Twentybytes always must be sent and received for communication with the PNOZmulti.
Ethernet/IP
The input/output data from the PNOZmulti can be polled using the assembly object (Class
04h).
} Data from the PNOZmulti are requested with instance64h.
} Instance 96h writes the data from the Ethernet IP scanner to the PNOZmulti.
Modbus TCP
No connection needs to be configured for the PNOZmc8p. Port 502 is used in accordance
with the Modbus TCP specification.
The Modbus TCP supports the following function codes:
3,16 and 23 (refer to the document "PNOZmulti Communication Interfaces" for details of
additional function codes)
The address input range begins with Register 0. The address output range begins with Re-
gister 1024. The Byte sequence for a Word is High Byte/Low Byte
Word
Left Byte Right Byte
Low Byte
(Bit 7 ... 00)
High Byte
(Bit 15 ... 08)
Input and output data
The data is structured as follows:
Input area
The inputs are defined in the master and transferred to the PNOZmulti. Each input has a
number, e.g. input bit 4 of byte 1 has the number I12.
Virtual inputs
PNOZmulti Configurator
I0 … I7 I8 … I15 I16 … I23 ... I120…I127
EtherNet/IP, Modbus
TCP
Byte 0:
Bit 0 … 7
Byte 1:
Bit 0 … 7
Byte 2:
Bit 0 … 7
... Byte 15:
Bit 0 … 7