Datasheet

PNOZmulti products
Fieldbus modules
PNOZ mc7p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
458
Fieldbus interface
Test voltage 500 V AC
Times
Supply interruption before de-energisation 20 ms
Environmental data
Ambient temperature
In accordance with the standard EN 60068-2-14
Temperature range 0 - 60 °C
Storage temperature
In accordance with the standard EN 60068-2-1/-2
Temperature range -25 - 70 °C
Climatic suitability
In accordance with the standard EN 60068-2-30, EN 60068-2-78
Humidity 93 % r. h. at 40 °C
Condensation during operation Not permitted
EMC EN 61131-2
Vibration
In accordance with the standard EN 60068-2-6
Frequency 10,0 - 150,0 Hz
Acceleration 1g
Shock stress
In accordance with the standard EN 60068-2-27
Acceleration 15g
Duration 11 ms
Max. operating height above sea level 2000 m
Airgap creepage
In accordance with the standard EN 61131-2
Overvoltage category III
Pollution degree 2
Rated insulation voltage 30 V
Protection type
In accordance with the standard EN 60529
Mounting area (e.g. control cabinet) IP54
Housing IP20
Terminals IP20
Potential isolation
Potential isolation between Fieldbus and module voltage
Type of potential isolation Functional insulation
Rated surge voltage 500 V
Mechanical data
Mounting position Horizontal on top hat rail