Datasheet

PNOZmulti products
Fieldbus modules
PNOZ mc5p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
429
Please note:
} Information given in the "Technical details" must be followed.
} Use copper wiring with a temperature stability of 75 °C.
Please note the following when connecting to INTERBUS:
} Only use metal plugs or metallised plastic plugs
} Twisted pair, screened cable must be used to connect the interfaces
Setting the transmission rate
The transmission rate is set using a jumper. You can choose between 500kBit/s and 2
MBit/s.
500 kBit/s:
500k 2M
2 MBit/s
500k 2M
Connecting the supply voltage
Connect the supply voltage to the base unit:
} Terminal 24 V and A1 (+): + 24VDC
} Terminal 0 V and A2 (-): 0 V
Download modified project to the PNOZmulti safety system
As soon as an additional expansion module has been connected to the system, the project
must be amended using the PNOZmulti Configurator. Proceed as described in the operat-
ing instructions for the base unit.