Datasheet

PNOZmulti products
Fieldbus modules
PNOZ mc5p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
428
Installation
Dimensions in mm
94 (3.70")
22,5
(0.88")
114 (4.49")
Commissioning
Preparing for commissioning
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
It is possible to define which outputs on the safety system will communicate with INTER-
BUS. The connection to INTERBUS is made via two female 9-pin D-Sub screw connectors
5
1
6
9
1: DO1
2: DI1
3: GND
4: n.c.
5: n.c.
6: /DO1
7: /DI1
8: n.c.
9: n.c.
IBS IN
1
5
9
6
1: DO2
2: DI2
3: GND
4: n.c.
5: GND
6: /DO2
7: /DI2
8: n.c.
9: RBST
IBS OUT
n. c. = not connected