Datasheet
PNOZmulti products
Link modules
PNOZ ml2p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
263
Insulation voltage test
The product PNOZ ml2p is connected to functional earth
via protection elements on the
supply voltage. Insulation voltage tests are only possible with voltages up to ca. 42 V.
Preparing for operation
Download modified project to the PNOZmulti safety system
As soon as an additional expansion module has been connected to the system, the project
must be amended using the PNOZmulti Configurator. Proceed as described in the operat-
ing instructions for the base unit.
Connection
Supply voltage AC DC
Supply voltage
Connection to a decentralised input module PDP67
CAN+
CAN-
VCC
GND
Shield
VCC
CAN-
GND
CAN+
Shield
PNOZ ml2p
PDP67 F 8DI ION
1
2
3
4
5