Datasheet
PNOZmulti products
Link modules
PNOZ ml2p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
262
Installation
Dimensions in mm
94 (3.70")
22,5
(0.88")
121 (4.76")
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
} Information given in the Technical details [
267] must be followed.
} Use copper wire that can withstand 75°C.
} Two connection terminals are available for each of the supply connections 24 V and 0 V
(semiconductor outputs), plus A1 and A2 (power supply). This means that the supply
voltage can be looped through several connections. When the supply voltage is looped,
the current at each terminal may not exceed 3A.
} Please refer to the technical details for information on the maximum cable length.
Please also read the section entitled Voltage drop [
265].
} Shielded cable must be used from a cable length of 30 m.
} Pilz pre-assembled cable can be used to connect the decentralised modules (see Order
references [
269]).
} The plug-in connection terminals are either designed as cage clamp terminals or screw
terminals (see Order references [
269]).