Datasheet

PNOZmulti products
Link modules
PNOZ ml1p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
251
Installation
Dimensions in mm
94 (3.70")
22,5
(0.88")
121 (4.76")
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
} Information given in the Technical details [
254] must be followed.
} Use copper wire that can withstand 75°C.
} Two connection terminals are available for each of the supply connections 24 V and 0 V
(semiconductor outputs), plus A1 and A2 (power supply). This means that the supply
voltage can be looped through several connections. When the supply voltage is looped,
the current at each terminal may not exceed 3A.
} The max. cable length between two link modules may be max. 1000 m.
Please note:
When connecting to a PNOZ ml1p with a version < 2.0, the cable length may be max.
100 m. The reduced cable length must be configured in the PNOZmulti Configurator.
} Connect the inputs and outputs from two PNOZ ml1p with a 4-core shielded cable. The
cables must be twisted in pairs (see "Preparing for operation").
} Note the crossover cabling, e.g. CA+ with CB+.
} The cables must be classified into a minimum of Category 5 in accordance with ISO/
IEC 11801.