Datasheet
PNOZmulti products
Analogue input module
PNOZ ma1p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
240
Installation
Dimensions
94 (3.70")
45
(1.77")
121 (4.76")
Commissioning
Wiring
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
} Information given in the Technical details [
242] must be followed.
} Use copper wire that can withstand 75°C.
} The power supply that feeds the expansion module and the input devices must meet
the regulations for extra low voltages with protective separation (SELV, PELV).
} 6 connection terminals are available for each of the supply connections 24 V and 0 V.
This means that the supply voltage can be looped through several connections and the
encoder can be supplied.
} Use shielded, twisted pair cable for the connections on the input current circuits.
} Separate the supply voltage cable from the analogue input current lines.
} If the analogue input module is used to measure current, the voltage inputs must be
short-circuited.
} For transducers located outside the control cabinet: Where the cable enters the
control cabinet, the cable shield must be connected to the earth potential over a wide
surface area and with low impedance (connect in star).