Datasheet

PNOZmulti products
Output modules
PNOZ mc1p
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2015-11
232
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram in the Configurator.
Please note:
} 2 connection terminals are available for each of the supply connections 24 V and 0 V.
This means that the supply voltage can be looped through several connections. The
current at each terminal may not exceed 3 A.
} Outputs OA0 to OA15 are auxiliary outputs using semiconductor technology.
} Use copper wiring with a temperature stability of 75 °C.
} Information given in the Technical details [
233] must be followed.
Connection
Supply voltage AC DC
24 V
+ 24 V DC
0 V
0 V
Supply voltage
OA0
L-
L-
OA1
Semiconductor outputs