PMD s10
NSG-D-2-422-2014-04Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Notice
][WICHTIG_PDB_alt
This data sheet is only intended for use
during configuration. For installation
and operation, please refer to the op-
erating instructions supplied with the
unit.
Montage
Technisch e Daten PMD s10
Technical details
Electrical data
Supply voltage U
B
AC/DC 24 - 240 V
Voltage tolerance -20 %/+10 %
Power consumption at U
B
AC 5.0 VA
Power consumption at U
B
DC 3.0 W
Frequency range AC 50 - 60 Hz
Utilisation category in accordance with EN 60947-4-1
Auxiliary contacts: AC1 at 240 V I
min
: 0.10 A , I
max
: 5.0 A
P
max
: 1200 VA
Auxiliary contacts: DC1 at 24 V I
min
: 0.10 A , I
max
: 5.0 A
P
max
: 120 W
Utilisation category in accordance with EN 60947-5-1
Auxiliary contacts: AC15 at 230 V I
max
: 5.0 A
Auxiliary contacts: DC13 at 24 V (6 cycles/min) I
max
: 2.0 A
Contact material AgNi10
External contact fuse protection (I
K
= 1 kA) to EN 60947-5-1
Blow-out fuse, quick
Auxiliary contacts: 6 A
Blow-out fuse, slow
Auxiliary contacts: 4 A
Circuit breaker 24 VAC/DC, characteristic B/C
Auxiliary contacts: 4 A
Times
Typ. response time of analogue output at DC 20 ms
Response time of analogue output at 15 ... 60 Hz 70 - 16 ms
Response time of analogue output at 60 ... 400 Hz 16 ms
Response time t
r
of auxiliary contact (selectable) 0.01 - 30.00 s
Start suppression time t
start
(selectable) 0.0 - 30.0 s
Measuring circuit
Measuring voltage U
M
(AC/DC) 100 - 550 V
Measuring current I
M
(AC/DC) 1 - 12 A
Frequency range 0, 15 - 400 Hz
Measuring range limit value (selectable) 1.0 W - 11.5 kW
Measuring range limit value P
max
with external current transformer 100.0 W - 11.5 MW
Performance range of 1 A current transformer 1.5 - 7.5 VA
Performance range of 5 A current transformer 2.5 - 15.0 VA
Current transformer class 3
Max. measuring current AC/DC 12 A
Temperature coefficient 0.10 %/K
Output signals during motor operation
Output voltage U
out
0... 10 V 0 - 10 V
Output voltage U
out
10 ... 0 V 10 - 0 V
Terminating impedance (apparent ohmic resistance) R
out
min. 1 kOhm
Output current I
out
4 ... 20 mA 4 - 20 mA
Output current I
out
0 ... 20 mA 0 - 20 mA
Terminating impedance (apparent ohmic resistance) R
out
max. 0.5 kOhm