Datasheet
Relays for functional safety
Safety relays PNOZsigma
PNOZ s30
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
850
} Start mode
– Rel.1 and semiconductor output Out 1, Rel.2 , Out 1, Out 2: Automatic start "Auto-
matic"
} Switch delay
None
} Max. encoder frequency
3.5 kHz
Basic settings for the rotary encoder
Settings for basic configuration 2
Level
Designation
on the display
Description Settings
1 Basic Parameter
Encoder:
Default
Load?
Select the default settings with
which the basic configuration
menu "Rotary encoder:" is to be
called:
- Load: The basic parameters are
loaded. Then it switches to the ba-
sic menu "Rotary encoder:".
The basic parameters should al-
ways be loaded when commis-
sioning for the first time.
- Edit: The basic parameters are
not loaded, i.e. all parameters are
retained. The basic menu para-
meters can be changed within the
permitted boundaries.
-Escape: Exits the basic menu.
2 Encoder
Default
TTL differential
Select rotary encoder type -TTL differential (A, /A, B, /B)
-TTL single ended (A, B)
-HTL differential (A, /A, B, /B)
-HTL single ended (A, B)
-sin/cos 1 Vss (A, /A, B, /B)
-Hiperface (A, /A, B, /B)
2 Standstill
Rel.1 Out 1
Default
100 Hz
Enter standstill frequency 10 mHz to 1.00 kHz