Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s30
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
825
The switch function with the lower number (e.g. F2) operates as the lower range limit;
the switch function with the higher number (e.g. F3) operates as the upper range limit.
Both switch functions can be assigned to one or more outputs.
} Position
Up to 4 different position windows can be monitored: Position 1 ... Position 4.
Each position to be monitored can be entered as often as necessary in parameter sets
P0 to P15 and switch functions F1 to F9.
} Direction
The monitoring functions "Direct. Left" and "Direct. Right" can be configured as a switch
function as often as necessary.
For both directions, a tolerance can be entered for the wrong direction.
Basic configuration
Two basic configurations are available for standard applications, for simple configuration
within the display menu. A basic configuration contains limited menu functions adapted for
standard applications, with partly pre-defined parameters.
The following basic configurations are available:
Basic configuration 1: Ini pnp pnp (proximity switch)
Pre-defined settings and configuration options:
} Encoder type
2 pnp type proximity switches
} Switch functions
Standstill (F1)
Standstill frequency configurable in Hz
Speed (F2)
Max. frequency (v max) configurable in Hz
} Parameter set/select input
P0, select inputs are ignored ("None" mode")
} Hysteresis
Standstill and speed, 2 % each
} Output assignment
Standstill: Relay output Rel. 1 and semiconductor output Out 1
Speed: Relay output Rel. 2 and semiconductor output Out 2
} Reset mode
Rel. 1, Rel. 2 Out 1, Out 2: Automatic reset
} Switch delay
None