Datasheet

Relays for functional safety
Safety relays PNOZsigma
PNOZ s4.1
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
616
Function description
}
In2+
Single-channel operation: no redundancy in the input circuit, earth faults in the start
circuit and input circuit are detected.
} Dual-channel operation without detection of shorts across contacts: Redundant input
circuit, detects PNOZ s4.1
earth faults in the start and input circuit,
short circuits in the input circuit and, with a monitored start, in the start circuit too.
}
In2-
Dual-channel operation with detection of shorts across contacts: Redundant input
circuit, detects PNOZ s4.1
earth faults in the start and input circuit,
Short circuits in the input circuit and, with a monitored start, in the start circuit too,
Shorts across contacts in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start Unit is active once the input circuit and the start circuit are closed.
} Monitored start with falling edge: Unit is active once
the input circuit is closed and then the start circuit is closed and opened again.
the start circuit is closed and then opened again once the input circuit is closed.
} Monitored start with rising edge: Unit is active once the input circuit is closed and
once the start circuit is closed after the waiting period has elapsed (seetechnical de-
tails).
} Start with start-up test: The unit checks whether safety gates that are closed are
opened and then closed again when supply voltage is applied.
} Increase in the number of available instantaneous safety contacts by connecting con-
tact expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expander module.