Inputs 777150 787150
Max. overall cable resistance Rl-
max
Single-channel at UB DC 120 Ohm 120 Ohm
Dual-channel without detection
of shorts across contacts at UB
DC 240 Ohm 240 Ohm
Dual-channel with detection of
shorts across contacts at UB DC 4 Ohm 4 Ohm
Semiconductor outputs 777150 787150
Number 2 2
Voltage 24 V 24 V
Current 20 mA 20 mA
External supply voltage 24 V 24 V
Voltage tolerance -20 %/+20 % -20 %/+20 %
Relay outputs 777150 787150
Number of output contacts
Safety contacts (N/O), instant-
aneous 5 5
Max. short circuit current IK 1 kA 1 kA
Utilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1
Utilisation category of safety con-
tacts
AC1 at 240 V 240 V
Min. current 0,01 A 0,01 A
Max. current 8 A 8 A
Max. power 2000 VA 2000 VA
DC1 at 24 V 24 V
Min. current 0,01 A 0,01 A
Max. current 8 A 8 A
Max. power 200 W 200 W
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at 230 V 230 V
Max. current 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 7 A 7 A