Datasheet

Relays for functional safety
Safety relays PNOZ X
PZE X4.1P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
430
Relay outputs 777588 787588
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 66 A²s 66 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24V AC/DC,
characteristic B/C 4 A 4 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Conventional thermal current
while loading several contacts
777588 787588
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 4,5 A 4,5 A
Conv. therm. current with 4 con-
tacts 3,5 A 3,5 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 4,5 A 4,5 A
Conv. therm. current with 4 con-
tacts 3,5 A 3,5 A
Times 777588 787588
Switch-on delay
With automatic start typ. 15 ms 15 ms
With automatic start max. 20 ms 20 ms
With automatic start after power
on typ. 230 ms 230 ms
With automatic start after power
on max. 360 ms 360 ms