Inputs 777540 777542 777544
Current at
Input circuit DC 35 mA 35 mA 35 mA
Start circuit DC 30 mA 30 mA 30 mA
Feedback loop DC 3 mA 3 mA 3 mA
Max. overall cable resist-
ance Rlmax
Single-channel at UB
DC 200 Ohm 200 Ohm 200 Ohm
Single-channel at UB
AC 200 Ohm 200 Ohm 200 Ohm
Dual-channel with de-
tection of shorts across
contacts at UB DC 20 Ohm 20 Ohm 20 Ohm
Dual-channel with de-
tection of shorts across
contacts at UB AC 20 Ohm 20 Ohm 20 Ohm
Relay outputs 777540 777542 777544
Number of output con-
tacts
Safety contacts (N/O),
instantaneous 2 2 2
Safety contacts (N/O),
delayed 2 2 2
Max. short circuit current
IK 1 kA 1 kA 1 kA
Utilisation category
In accordance with the
standard EN 60947-4-1 EN 60947-4-1 EN 60947-4-1
Utilisation category of
safety contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 2000 VA 2000 VA 2000 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 200 W 200 W 200 W