Datasheet

Relays for functional safety
Safety relays PNOZ X
PNOZ XV1P
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com
2016-09
280
Inputs 777601 777602
Current at
Input circuit DC 35 mA 35 mA
Start circuit DC 35 mA 35 mA
Feedback loop DC 3,5 mA 3,5 mA
Max. overall cable resistance Rl-
max
Single-channel at UB DC 100 Ohm 100 Ohm
Dual-channel without detection
of shorts across contacts at UB
DC 150 Ohm 150 Ohm
Dual-channel with detection of
shorts across contacts at UB DC 15 Ohm 15 Ohm
Relay outputs 777601 777602
Number of output contacts
Safety contacts (N/O), instant-
aneous 2 2
Safety contacts (N/O), delayed 1 1
Max. short circuit current IK 1 kA 1 kA
Utilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1
Utilisation category of safety con-
tacts
AC1 at 240 V 240 V
Min. current 0,01 A 0,01 A
Max. current 5 A 5 A
Max. power 1250 VA 1250 VA
DC1 at 24 V 24 V
Min. current 0,01 A 0,01 A
Max. current 5 A 5 A
Max. power 125 W 125 W
Utilisation category of safety con-
tacts delayed
AC1 at 240 V 240 V
Min. current 0,01 A 0,01 A
Max. current 5 A 5 A
Max. power 1250 VA 1250 VA
DC1 at 24 V 24 V
Min. current 0,01 A 0,01 A
Max. current 5 A 5 A
Max. power 125 W 125 W
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1